NYY-J NYY-O Cable
NYY-J NYY-O Cable
NYY-J NYY-O Cable 0.6/1 kV Power and control cables for fixed installation.
Can be used indoors, outdoors, underground, in concrete and in water
Application
The NYY cable range includes NYY-J and NYY-O cables. Power and control cables for fixed installation. Can be used indoors, outdoors, underground, in concrete and in water.
Advantages of the NYY-O and NYY-J
Flame retardant
Cables used to be responsible for spreading fire. The NYY-O and NYY-J are flame retardant. This means that these cables are designed in a way that it will not spread fire. Cables with these advantages are often used in buildings and at locations where people live, work and travel / move.
UV resistant*
Cables that are not UV resistant will be affected when they are exposed to direct sunlight. Only the cables with a black outer sheath have a UV-stabilised outer sheath making them suitable for direct exposure to sunlight. The outer sheath of the cable will not be harmed by the ultra-violet light which normally dries out a cable or causes cracks or bursts in the sheath. This will preserve the functionality of the cable.
Product Features
Voltage Uo/U: 0.6/1kV
Temperature rating: Fixed: -15ºC to +70ºC, Flexing: -5ºC to +50ºC
Specifications
Cable structure
Cores Solid or stranded of copper wires according to DIN VDE O295 cl.1 or cl.2
Core insulation
PVC
Color coding
Up to 5 cores, color coding according to DIN VDE 0293 For cables with 7 cores and up, black cores withwhite numbering Green/Yellow earthing core -J in the outer layer
Wrapping
Massive filling of thermoplastic
Outer sheath
PVC according to HD 603.1, black color, self extingushing andflame retardant according to DIN VDE 0482 and lEC 60332-1
NYY-J with earthcore
NYY-0 without earthing core
Parameter
DIMENSIONS | |||||
NO. OF CORES | NOMINAL CROSS SECTIONAL AREA | NOMINAL THICKNESS OF INSULATION | NOMINAL THICKNESS OF SHEATH | NOMINAL OVERALL DIAMETER | NOMINAL WEIGHT |
mm2 | mm | mm | mm | kg/km | |
1 | 2.5 | 0.8 | 1.4 | 6.15 | 62 |
1 | 4 | 1 | 1.4 | 7.5 | 85 |
1 | 6 | 1 | 1.4 | 7.5 | 108 |
1 | 10 | 1 | 1.4 | 8.6 | 155 |
1 | 16 | 1 | 1.4 | 9.6 | 218 |
1 | 25 | 1.2 | 1.4 | 11.1 | 318 |
1 | 35 | 1.2 | 1.4 | 12.1 | 414 |
1 | 50 | 1.4 | 1.4 | 13.7 | 552 |
1 | 70 | 1.4 | 1.4 | 15.5 | 750 |
1 | 95 | 1.6 | 1.5 | 17.6 | 1020 |
1 | 120 | 1.6 | 1.6 | 19.3 | 1259 |
1 | 150 | 1.8 | 1.6 | 21 | 1546 |
1 | 185 | 2 | 1.7 | 23.2 | 1913 |
1 | 240 | 2.2 | 1.8 | 26.2 | 2471 |
1 | 300 | 2.4 | 2 | 29.2 | 3097 |
2 | 1.5 | 0.8 | 1.8 | 10 | 147 |
2 | 2.5 | 0.8 | 1.8 | 10.7 | 179 |
2 | 4 | 1 | 1.8 | 13 | 268 |
2 | 6 | 1 | 1.8 | 14.2 | 337 |
2 | 10 | 1 | 1.8 | 16.2 | 472 |
2 | 16 | 1 | 1.8 | 18.2 | 644 |
3 | 1.5 | 0.8 | 1.8 | 10.4 | 166 |
3 | 2.5 | 0.8 | 1.8 | 11.3 | 212 |
3 | 4 | 1 | 1.8 | 13.1 | 299 |
3 | 6 | 1 | 1.8 | 15 | 402 |
3 | 10 | 1 | 1.8 | 17.1 | 570 |
3 | 16 | 1 | 1.8 | 19.2 | 789 |
3 | 25 | 1.2 | 1.8 | 22.1 | 1141 |
3 | 35 | 1.2 | 1.8 | 24.1 | 1462 |
3 | 50 | 1.4 | 1.8 | 27.6 | 1964 |
3 | 70 | 1.6 | 2.1 | 36.3 | 3635 |
3 | 95 | 1.6 | 2.2 | 40 | 4488 |
4 | 1.5 | 0.8 | 1.8 | 11.6 | 198 |
4 | 2.5 | 0.8 | 1.8 | 12.1 | 252 |
4 | 4 | 1 | 1.8 | 15.1 | 391 |
4 | 6 | 1 | 1.8 | 16.5 | 465 |
4 | 10 | 1 | 1.8 | 18.6 | 702 |
4 | 16 | 1 | 1.8 | 21.1 | 992 |
4 | 25 | 1.2 | 1.8 | 24.2 | 1431 |
4 | 35 | 1.2 | 1.8 | 26.6 | 1861 |
4 | 50 | 1.4 | 1.9 | 30.9 | 2535 |
4 | 70 | 1.4 | 2.1 | 35.1 | 3441 |
4 | 95 | 1.6 | 2.2 | 40.4 | 4691 |
4 | 120 | 1.6 | 2.4 | 44.2 | 5757 |
4 | 150 | 1.8 | 2.5 | 48.5 | 7095 |
4 | 185 | 2 | 2.7 | 53.9 | 8810 |
4 | 240 | 2.2 | 2.9 | 61.1 | 11400 |
5 | 1.5 | 10.8 | 1.8 | 12 | 232 |
5 | 2.5 | 0.8 | 1.8 | 13.1 | 302 |
5 | 4 | 1 | 1.8 | 16.6 | 477 |
5 | 6 | 1 | 1.8 | 18.2 | 618 |
5 | 10 | 1 | 1.8 | 20.3 | 853 |
5 | 16 | 1 | 1.8 | 23.1 | 1212 |
5 | 25 | 0.8 | 1.8 | 26.6 | 280 |
7 | 1.5 | 1 | 1.8 | 16.6 | 477 |
7 | 2.5 | 0.8 | 1.8 | 14.1 | 368 |
12 | 1.5 | 0.8 | 1.8 | 16.6 | 475 |
12 | 2.5 | 0.8 | 1.8 | 18.2 | 628 |
14 | 1.5 | 0.8 | 1.8 | 17.1 | 515 |
19 | 1.5 | 0.8 | 1.8 | 18.9 | 648 |
19 | 2.5 | 0.8 | 1.8 | 20.3 | 843 |
27 | 1.5 | 0.8 | 1.8 | 22.6 | 895 |
PDF Download
PDF Download
Why Choose Us
Contact Us Immediately
Contact Us
- 24-hour online service
- Own factory processing
Product Category
hot-sale product
600/1000V XLPE Insulation Armoured Power Cable Single core( aluminum wire armoured)
600/1000V XLPE Insulation Armoured Power Cable Two cores(Galvanized steel wire armoured)
600/1000V XLPE Insulation Armoured Power Cable Three cores(Galvanized steel wire armoured)
600/1000V XLPE Insulation Armoured Power Cable Three cores+1(Galvanized steel wire armoured)
600/1000V XLPE Insulation Armoured Power Cable Four cores(Galvanized steel wire armoured)
600/1000V XLPE Insulation Unarmoured Power Cables are used for power supply in low voltage installation systems,
Suitable for installation indoors and outdoors, in cable ducts, underground, in power stations and switchyards, local energy distribution, industrial plants, without risk of mechanical damage
PVC insulated Unarmoured power cable
PVC insulated armored power cable
CU/PVC/PVC/SWA/PVC
CU/PVC/SWA/PVC