SAC Spaced Aerial Cable(ICEA S-66-524)
SAC Spaced Aerial Cable(ICEA S-66-524)
Cable Structure: POLYETHYLENE INSULATED
Conductor: Compact stranded hard drawn Aluminium wire.
Conductor Sizes: 35 – 185 mm2
Insulation: Track resistant cross-linked polyethylene (Black)
Application: For used in primary aerial cable on pole.
Application
This kind of spaced aerial cable ( SAC cable) is used for aerial power transmission at 15/25/35 maximum system voltage. the phase to phase voltage is 10/20/33KV. This standard applies of supported spacer cable. These conductors are intended primarily for the distribution of electrical energy under normal conditions of overhead (aerial) installations. They are considered as covered conductors therefore the cables carry no voltage rating. The conductors must be installed on insulators and/or spacers adequate for the service voltage. The user may want to give consideration to the dielectric compatibility of the covering, insulator, spacer.
The conductors are stranded,circular compressed aluminum. The conductor screen is the extruded Semi-conducting conductor shield in Black. The inner Insulation is mainly natural color thermoplastic polyethylene (PE) or cross-linked polyethylene (XLPE). And the outer Insulation is mainly thermoplastic polyethylene (PE) or cross-linked polyethylene (XLPE) in Black or Grey with Weather or UV resistant. This standard covers both thermoplastic and cross linked polyethylene constructions, rated for 75°C or 90°C normal service temperature.
Specifications
• ICEA S-66-524 Cross-Linked-Thermosetting-Polyethylene-Insulated Wire and Cable for The Transmission and Distribution of Electrical Energy
• GB/T 14049 (Equal to IEC 60502-2) Aerial Insulated Cables For Rated Voltage of 10kV
Parameter
Nominal Size | Min.No. of Wires |
Covering Thickness | Cable Diameter | Min. Breaking Load | Weight | |||
Conductor Shield | Inner Layer | Outer Layer | ||||||
mm2 | No. | mm | mm | mm | mm | N | kg/km | |
3-Layer 15kV AAC/XLPE/XLPE | ||||||||
25 | 6 | 0.60 | 1.91 | 1.91 | 15.2 | 3762 | 218 | |
35 | 6 | 0.60 | 1.91 | 1.91 | 16.2 | 5177 | 258 | |
50 | 6 | 0.60 | 1.91 | 1.91 | 17.3 | 7011 | 307 | |
70 | 12 | 0.60 | 1.91 | 1.91 | 19.0 | 10354 | 387 | |
95 | 15 | 0.60 | 1.91 | 1.91 | 20.8 | 13727 | 482 | |
120 | 15 | 0.60 | 1.91 | 1.91 | 22.0 | 17339 | 564 | |
150 | 15 | 0.60 | 1.91 | 1.91 | 23.7 | 21033 | 660 | |
185 | 30 | 0.60 | 1.91 | 1.91 | 25.3 | 26732 | 780 | |
240 | 30 | 0.60 | 1.91 | 1.91 | 27.6 | 34679 | 968 |
Nominal Size | Min. No. of Wires |
Covering Thickness | Cable Diameter | Min. Breaking Load | Weight | ||
Conductor Shield | Inner Layer | Outer Layer | |||||
mm2 | No. | mm | mm | mm | mm | N | kg/km |
3-Layer 25kV AAC/XLPE/XLPE | |||||||
25 | 6 | 0.70 | 3.18 | 3.18 | 20.1 | 3762 | 351 |
35 | 6 | 0.70 | 3.18 | 3.18 | 21.1 | 5177 | 398 |
50 | 6 | 0.70 | 3.18 | 3.18 | 22.2 | 7011 | 455 |
70 | 12 | 0.70 | 3.18 | 3.18 | 23.9 | 10354 | 548 |
95 | 15 | 0.70 | 3.18 | 3.18 | 25.7 | 13727 | 657 |
120 | 15 | 0.70 | 3.18 | 3.18 | 26.9 | 17339 | 748 |
150 | 15 | 0.70 | 3.18 | 3.18 | 28.6 | 21033 | 856 |
185 | 30 | 0.70 | 3.18 | 3.18 | 30.2 | 26732 | 989 |
240 | 30 | 0.70 | 3.18 | 3.18 | 32.5 | 34679 | 1195 |
Nominal Size | Min. No. of Wires |
Covering Thickness | Cable Diameter | Min. Breaking Load | Weight | ||
Conductor Shield | Inner Layer | Outer Layer | |||||
mm2 | No. | mm | mm | mm | mm | N | kg/km |
3-Layer 35kV AAC/XLPE/XLPE | |||||||
25 | 6 | 0.70 | 4.45 | 3.18 | 22.6 | 3762 | 433 |
35 | 6 | 0.70 | 4.45 | 3.18 | 23.6 | 5177 | 485 |
50 | 6 | 0.70 | 4.45 | 3.18 | 24.7 | 7011 | 545 |
70 | 12 | 0.70 | 4.45 | 3.18 | 26.4 | 10354 | 645 |
95 | 15 | 0.70 | 4.45 | 3.18 | 28.2 | 13727 | 761 |
120 | 15 | 0.70 | 4.45 | 3.18 | 29.4 | 17339 | 856 |
150 | 15 | 0.70 | 4.45 | 3.18 | 31.1 | 21033 | 971 |
185 | 30 | 0.70 | 4.45 | 3.18 | 32.7 | 26732 | 1110 |
240 | 30 | 0.70 | 4.45 | 3.18 | 35.0 | 34679 | 1324 |
Nominal Size | Min. No. of Wires |
Covering Thickness | Cable Diameter | Min. Breaking Load | Weight | |||
Conductor Shield | Inner Layer | Outer Layer | ||||||
mm2 | No. | mm | mm | mm | mm | N | kg/km | |
3-Layer 15kV AAC/XLPE/HDPE | ||||||||
25 | 6 | 0.60 | 1.91 | 1.91 | 15.2 | 3762 | 221 | |
35 | 6 | 0.60 | 1.91 | 1.91 | 16.2 | 5177 | 261 | |
50 | 6 | 0.60 | 1.91 | 1.91 | 17.3 | 7011 | 310 | |
70 | 12 | 0.60 | 1.91 | 1.91 | 19.0 | 10354 | 390 | |
95 | 15 | 0.60 | 1.91 | 1.91 | 20.8 | 13727 | 486 | |
120 | 15 | 0.60 | 1.91 | 1.91 | 22.0 | 17339 | 568 | |
150 | 15 | 0.60 | 1.91 | 1.91 | 23.7 | 21033 | 664 | |
185 | 30 | 0.60 | 1.91 | 1.91 | 25.3 | 26732 | 785 | |
240 | 30 | 0.60 | 1.91 | 1.91 | 27.6 | 34679 | 973 |
Nominal Size | Min. No. of Wires |
Covering Thickness | Cable Diameter | Min. Breaking Load | Weight | ||
Conductor Shield | Inner Layer | Outer Layer | |||||
mm2 | No. | mm | mm | mm | mm | N | kg/km |
3-Layer 25kV AAC/XLPE/HDPE | |||||||
25 | 6 | 0.70 | 3.18 | 3.18 | 20.1 | 3762 | 356 |
35 | 6 | 0.70 | 3.18 | 3.18 | 21.1 | 5177 | 404 |
50 | 6 | 0.70 | 3.18 | 3.18 | 22.2 | 7011 | 461 |
70 | 12 | 0.70 | 3.18 | 3.18 | 23.9 | 10354 | 555 |
95 | 15 | 0.70 | 3.18 | 3.18 | 25.7 | 13727 | 664 |
120 | 15 | 0.70 | 3.18 | 3.18 | 26.9 | 17339 | 755 |
150 | 15 | 0.70 | 3.18 | 3.18 | 28.6 | 21033 | 864 |
185 | 30 | 0.70 | 3.18 | 3.18 | 30.2 | 26732 | 997 |
240 | 30 | 0.70 | 3.18 | 3.18 | 32.5 | 34679 | 1203 |
Nominal Size | Min. No. of Wires |
Covering Thickness | Cable Diameter | Min. Breaking Load | Weight | ||
Conductor Shield | Inner Layer | Outer Layer | |||||
mm2 | No. | mm | mm | mm | mm | N | kg/km |
3-Layer 35kV AAC/XLPE/HDPE | |||||||
25 | 6 | 0.70 | 4.45 | 3.18 | 22.6 | 3762 | 439 |
35 | 6 | 0.70 | 4.45 | 3.18 | 23.6 | 5177 | 491 |
50 | 6 | 0.70 | 4.45 | 3.18 | 24.7 | 7011 | 552 |
70 | 12 | 0.70 | 4.45 | 3.18 | 26.4 | 10354 | 652 |
95 | 15 | 0.70 | 4.45 | 3.18 | 28.2 | 13727 | 768 |
120 | 15 | 0.70 | 4.45 | 3.18 | 29.4 | 17339 | 864 |
150 | 15 | 0.70 | 4.45 | 3.18 | 31.1 | 21033 | 980 |
185 | 30 | 0.70 | 4.45 | 3.18 | 32.7 | 26732 | 1119 |
240 | 30 | 0.70 | 4.45 | 3.18 | 35.0 | 34679 | 1334 |
PDF Download
PDF Download
Why Choose Us
Contact Us Immediately
Contact Us
- 24-hour online service
- Own factory processing
Product Category
hot-sale product
Including 1, 2, 3, 4, 5, 1+1, 2+1, 3+1, 4+1 cores and so on, from 10mm2 to 240mm2 as follows, 10mm2 16mm2 25mm2 35mm2 50mm2 70mm2 95mm2 120mm2 150mm2 185mm2 240m2.
Conductor: 1350-H19 Aluminum conductor, H68 round stranded conpressed(RM) Aluminium Conductor
Insulation: XLPE or PE or PVC, UV-resistant.
XLPE covered aerial cables to AS/NZS 3675.
Water-blocked aluminium alloy 1120 conductors.
Also available with XLPE/HDPE covering.
Phase conductor: Aluminum, class 2,circular compacted conductors
Phase conductor screen: Non-metallic,semi-conducting compound
Phase insulation:Cross-linked polyethylene(XLPE)
Phase insulation screen:Non-metallic,semi-conducting compound,extruded strippable grooved elastomer
Phase longitudinal water tightness: Swelling powder
Phase metallic screen: Aluminium plastic tape (AL/PET)
Phase outer sheath: Polyethylene (PE)
Messenger conductor: Stranded galvanized steel wires
Messenger insulation: Polyethylene (PE)Specification
Duplex/Triplex/Quadruplex Service Drop Cable
Aluminum Overhead Service Drop Cable
LV Overhead insulated Cable
Overhead Service Cable
Overhead Line & Transmission Cables