Aerial Insulated Cable (IEC 60502-1)
Aerial Insulated Cable (IEC 60502-1)
CU/PVC, AAC/PVC, AAAC/PVC, CU/PE, AAC/PE, AAAC/PE
CU/XLPE, AAC/XLPE, AAAC/XLPE
AAC/PVC, AAC/PE, AAC/XLPE
Application
The IEC 60502-1 standard Aerial Insulated Cable LV ABC Cable Aerial Bundle Conductor is overhead power lines and room entrance wires with a rated AC pressure of 1kv and below. ABC Cable has less installation, maintenance, and operating costs, which can achieve greater economic loss and provide higher security and reliability.
Aerial Bundle Cable (ABC cable) is a very innovative concept for overhead power distribution as compared to the conventional bare conductor overhead distribution system.
LV Aerial Bundle Cables are designed to supply 600/1000 volt aerial service for temporary service at construction sites, as a service drop (power pole to service entrance), as a secondary cable (pole to pole) or street lighting.
Construction
Conductor: Conductors are stranded,circular compacted or uncompacted aluminum, copper , aluminum-alloy, ACSR etc.
Insulation: Thermoplastic polyethylene(PE),polyvinyl chloride (PVC) ,cross-linked polyethylene (XLPE),black color,weather and UV resistant.
Specifications
● GB/T 12527(Equivalent to IEC 60502-1)Aerial Insulated Cables for Rated Voltages up to and Including 1kV
● IEC 60228 Conductors of insulated cables
Parameter
| Section Area | Phase Core | Neutral Core | Complete Cable | |||||||
| Section Area | No. of Wires | Conductor Diameter | Insulation Thickness | Section Area | No. of Wire | Conductor Diameter | Insulation Thickness | Approx. Diameter |
Approx. Weight |
|
| mm2 | mm2 | No. | mm | mm | mm2 | No. | mm | mm | mm | kg/km |
| 1×10 | 1×10 | 7 | 4.05 | 1.0 | – | – | – | – | 6.1 | 43 |
| 1×16 | 1×16 | 7 | 4.8 | 1.2 | – | – | – | – | 7.2 | 64 |
| 1×25 | 1×25 | 7 | 6 | 1.2 | – | – | – | – | 8.4 | 92 |
| 1×35 | 1×35 | 7 | 7 | 1.4 | – | – | – | – | 9.8 | 127 |
| 1×50 | 1×50 | 7 | 8.1 | 1.4 | – | – | – | – | 11.1 | 165 |
| 1×70 | 1×70 | 19 | 10 | 1.4 | – | – | – | – | 12.8 | 230 |
| 1×95 | 1×95 | 19 | 11.6 | 1.6 | – | – | – | – | 14.8 | 315 |
| 1×120 | 1×120 | 19 | 13 | 1.6 | – | – | – | – | 16.2 | 390 |
| 1×150 | 1×150 | 19 | 14.6 | 1.8 | – | – | – | – | 18.2 | 476 |
| 1×185 | 1×185 | 37 | 16.2 | 2 | – | – | – | – | 20.2 | 609 |
| 2×10 | 2×10 | 7 | 4 | 1 | – | – | – | – | 12.2 | 85 |
| 2×16 | 2×16 | 7 | 4.8 | 1.2 | – | – | – | – | 14.4 | 128 |
| 2×25 | 2×25 | 7 | 6 | 1.2 | – | – | – | – | 16.8 | 184 |
| 2×35 | 2×35 | 7 | 7 | 1.4 | – | – | – | – | 19.6 | 255 |
| 2×50 | 2×50 | 7 | 8.1 | 1.4 | – | – | – | – | 22.2 | 329 |
| 2×70 | 2×70 | 19 | 10 | 1.4 | – | – | – | – | 25.6 | 459 |
| 3×10 | 3×10 | 7 | 4 | 1 | – | – | – | – | 13.1 | 128 |
| 3×16 | 3×16 | 7 | 4.8 | 1.2 | – | – | – | – | 17.4 | 192 |
| 3×25 | 3×25 | 7 | 6 | 1.2 | – | – | – | – | 20.3 | 276 |
| 3×35 | 3×35 | 7 | 7 | 1.4 | – | – | – | – | 21.1 | 382 |
| 3×50 | 3×50 | 7 | 8.1 | 1.4 | – | – | – | – | 23.9 | 494 |
| 3×70 | 3×70 | 19 | 10 | 1.4 | – | – | – | – | 27.6 | 688 |
| 3×95 | 3×95 | 19 | 11.6 | 1.6 | – | – | – | – | 31.9 | 943 |
| 3×120 | 3×120 | 19 | 13 | 1.6 | – | – | – | – | 34.9 | 1170 |
| 4×10 | 4×10 | 7 | 4 | 1 | – | – | – | – | 14.6 | 171 |
| 4×16 | 4×16 | 7 | 4.8 | 1.2 | – | – | – | – | 17.4 | 256 |
| 4×25 | 4×25 | 7 | 6 | 1.2 | – | – | – | – | 20.3 | 368 |
| 4×35 | 4×35 | 7 | 7 | 1.4 | – | – | – | – | 23.7 | 509 |
| 4×50 | 4×50 | 7 | 8.1 | 1.4 | – | – | – | – | 26.8 | 659 |
| 4×70 | 4×70 | 19 | 10 | 1.4 | – | – | – | – | 30.9 | 917 |
| 4×95 | 4×95 | 19 | 11.6 | 1.6 | – | – | – | – | 35.8 | 1258 |
| 4×120 | 4×120 | 19 | 13 | 1.6 | – | – | – | – | 39.1 | 1559 |
| 1×16+16 | 1×16 | 7 | 4.8 | 1.2 | 1×16 | 7 | 5.1 | – | 12.3 | 108 |
| 1×25+25 | 1×25 | 7 | 6 | 1.2 | 1×25 | 7 | 6.3 | – | 14.7 | 158 |
| 1×35+35 | 1×35 | 7 | 7 | 1.4 | 1×35 | 7 | 7.5 | – | 17.3 | 221 |
| 1×50+50 | 1×50 | 7 | 8.4 | 1.4 | 1×50 | 7 | 9 | – | 20.1 | 300 |
| 2×16+16 | 2×16 | 7 | 4.8 | 1.2 | 1×16 | 7 | 5.1 | – | 15.5 | 172 |
| 2×25+25 | 2×25 | 7 | 6 | 1.2 | 1×25 | 7 | 6.3 | – | 18.1 | 250 |
| 2×35+35 | 2×35 | 7 | 7 | 1.4 | 1×35 | 7 | 7.5 | – | 21.1 | 348 |
| 2×50+50 | 2×50 | 7 | 8.3 | 1.4 | 1×50 | 7 | 9 | – | 22.4 | 464 |
| 3×16+16 | 3×16 | 7 | 4.8 | 1.2 | 1×16 | 7 | 5.1 | – | 17.4 | 235 |
| 3×25+25 | 3×25 | 7 | 6 | 1.2 | 1×25 | 7 | 6.3 | – | 20.3 | 342 |
| 3×35+35 | 3×35 | 7 | 7 | 1.4 | 1×35 | 7 | 7.5 | – | 23.7 | 475 |
| 3×50+50 | 3×50 | 7 | 8.1 | 1.4 | 1×50 | 7 | 9 | – | 26.8 | 629 |
| 3×70+70 | 3×70 | 19 | 10 | 1.4 | 1×70 | 19 | 10.5 | – | 30.9 | 869 |
| 3×95+95 | 3×95 | 19 | 11.6 | 1.6 | 1×95 | 19 | 12.5 | – | 35.7 | 1200 |
| 3×35+16 | 3×35 | 7 | 7 | 1.4 | 1×16 | 7 | 4.8 | – | 22.2 | 445 |
| 3×50+25 | 3×50 | 7 | 8.1 | 1.4 | 1×25 | 7 | 6 | – | 24.8 | 585 |
| 3×70+35 | 3×70 | 19 | 10 | 1.4 | 1×35 | 7 | 7 | – | 30.9 | 815 |
| 3×95+50 | 3×95 | 19 | 11.6 | 1.6 | 1×50 | 7 | 8.1 | – | 35.7 | 1108 |
| 4×95+35 | 4×95 | 19 | 11.6 | 1.6 | 1×35 | 7 | 7 | – | 39.9 | 1385 |
| 3×120+70 | 3×120 | 19 | 13 | 1.6 | 1×70 | 19 | 10 | – | 39.1 | 1399 |
| NUMBER OF CORES X NOMINAL CROSS SECTION | OVERAL DIAMETER | WEIGHT | MAXIMUM CONDUCTOR RESISTANCE | MINIMUM BREAKING LOAD | CURRENT RATING |
|---|---|---|---|---|---|
| NO.×MM² | MM | KG/KM | Ω/KM | KN | A |
| 1×16+1×25 RM | 15.3 | 160 | 1.910 | 2.5 | 72 |
| 3×16+1×25 RM | 19.0 | 290 | 1.200 | 4.0 | 107 |
| 3×25+1×25 RM | 23.2 | 400 | 0.868 | 5.5 | 132 |
| 3×35+1×25 RM | 25.6 | 500 | 0.641 | 8.0 | 165 |
| 3×50+1×35 RM | 30.0 | 680 | 0.443 | 10.7 | 205 |
| 3×70+1×50 RM | 34.9 | 920 | 0.320 | 13.7 | 240 |
| 3×95+1×70 RM | 40.6 | 1270 | 0.253 | 18.6 | 290 |
| 3×120+1×70 RM | 44.1 | 1510 | 0.206 | 23.2 | 334 |
| 3×150+1×95 RM | 49.2 | 1870 | 0.164 | 28.7 | 389 |
| 3×185+1×120 RM | 54.9 | 2340 | 0.125 | 37.2 | 467 |
| 3×25+1×25+1×16 RM | 23.2 | 470 | 1.910 | 2.5 | 72 |
| 3×35+1×25+1×16 RM | 25.6 | 560 | 1.200 | 4.0 | 107 |
| 3×50+1×35+1×16 RM | 30.0 | 740 | 0.868 | 5.5 | 132 |
| 3×70+1×50+1×16 RM | 34.9 | 980 | 0.641 | 8.0 | 165 |
| 3×95+1×70+1×16 RM | 40.6 | 1330 | 0.443 | 10.7 | 205 |
| 3×120+1×70+1×16 RM | 44.1 | 1580 | 0.320 | 13.7 | 240 |
| 3×150+1×95+1×16 RM | 49.2 | 1940 | 0.206 | 23.2 | 334 |
| 3×185+1×120+1×16 RM | 54.9 | 2410 | 1.910 | 2.5 | 72 |
| Number of cores x nominal cross section | min. breaking load of conductor strand | Current rating in the air | Outer diameter | Total weight |
| mm² | kN | A | mm | kg/km |
| 4×25 RM | 3.5 | 84 | 21.5 | 420 |
| 4×35 RM | 4.9 | 104 | 23.9 | 550 |
| 4×120+1×25 RM | 16.8 | 246 | 43.8 | 1800 |
| 4×185+1×25 RM | 25.9 | 332 | 50.7 | 2700 |
PDF Download
PDF Download
Why Choose Us
Contact Us Immediately
Contact Us
- 24-hour online service
- Own factory processing
Product Category
hot-sale product
XLPE covered aerial cables to AS/NZS 3675.
Water-blocked aluminium alloy 1120 conductors.
Also available with XLPE/HDPE covering.
Phase conductor: Aluminum, class 2,circular compacted conductors
Phase conductor screen: Non-metallic,semi-conducting compound
Phase insulation:Cross-linked polyethylene(XLPE)
Phase insulation screen:Non-metallic,semi-conducting compound,extruded strippable grooved elastomer
Phase longitudinal water tightness: Swelling powder
Phase metallic screen: Aluminium plastic tape (AL/PET)
Phase outer sheath: Polyethylene (PE)
Messenger conductor: Stranded galvanized steel wires
Messenger insulation: Polyethylene (PE)Specification
ANSI/ICEA S-121-733 Tree Wire and Messenger Supported Spacer Cable
Covered Aerial MV Cable (Spacer Cable or Tree Wire)
5kv 15kv 25kv 35kv 46kv AAC AAAC ACSR Tree Wire Conductor
Cable Torsadé Aluminium; Câble Torsadé Aérien; Câble électrique Aérien
Phase Conductor: Aluminium conductor, round stranded compressed (RM).
Neutral Conductor: Alloy aluminium conductor (AlMgSi), round stranded compressed (RM).
Insulation: XLPE. Load-bearing / neutral core – marked with standard and producers phase core – marked with digits 1, 2, 3.
Assembly: Cores and the neutral, conductor stranded together in right-hand lay, additionally 1, 2 or 3 cores of reduced cross section can be co-stranded.