Aerial Bundled Cable (NFC 33-209)
Aerial Bundled Cable (NFC 33-209)
Cable Torsadé Aluminium; Câble Torsadé Aérien; Câble électrique Aérien
Phase Conductor: Aluminium conductor, round stranded compressed (RM).
Neutral Conductor: Alloy aluminium conductor (AlMgSi), round stranded compressed (RM).
Insulation: XLPE. Load-bearing / neutral core – marked with standard and producers phase core – marked with digits 1, 2, 3.
Assembly: Cores and the neutral, conductor stranded together in right-hand lay, additionally 1, 2 or 3 cores of reduced cross section can be co-stranded.
Application
Cable Aérien Torsadé NFC 33-209 insulated cable assembled with harness for overhead network, with rated voltage of 0.6/1kV.
Primarily used for overhead service applications such as street lighting, outdoor lighting, and temporary service for construction. To be used at voltages of 0.6/1kV and at conductor temperatures not to exceed 90°C for cross-linked polyethylene (XLPE) insulated conductors.
Construction
Conductor: Stranded,Circular compacted ,Circular compressed AAC or AAAC.
Insulation: Cross-linked polyethylene (XLPE),Black color,Weather and UV resistant.
Specifications
NFC 33-209 insulated cable assembled with harness for overhead network, with rated voltage of 0.6/1kV
| PHASE CONDUCTOR | Aluminium conductor, round stranded compressed (RM). |
|---|---|
| NEUTRAL CONDUCTOR | Alloy aluminium conductor (AlMgSi), round stranded compressed (RM). |
| INSULATION | XLPE. Load-bearing / neutral core – marked with standard and producers phase core – marked with digits 1, 2, 3. |
| ASSEMBLY | Cores and the neutral, conductor stranded together in right-hand lay, additionally 1, 2 or 3 cores of reduced cross section can be co-stranded. |
Parameter
| NUMBER OF CORES X NOMINAL CROSS SECTION | MAX. CONDUCTOR- RESISTANCE | MIN. BREAKING LOAD OF CONDUCTOR STRAND | CURRENT RATING IN THE AIR | OUTER DIAMETER | TOTAL WEIGHT |
|---|---|---|---|---|---|
| MM² | OHM/KM | KN | A | MM | KG/KM |
| 2×10 RM | 3.080 | 1.5 | 38 | 12.8 | 93 |
| 4×10 RM | 3.080 | 1.5 | 38 | 15.4 | 183 |
| 2×16 RM | 1.910 | 2.3 | 72 | 14.8 | 129 |
| 2×16 RN + 2×1.5 RE | 1.910/12.100 | 2.3 | 72 | 14.8 | 176 |
| 4×16 RM | 1.910 | 2.3 | 72 | 17.8 | 257 |
| 4×16 RN + 2×1.5 RE | 1.910/12.100 | 2.3 | 72 | 17.8 | 304 |
| 2×25 RM | 1.200 | 3.8 | 107 | 18.0 | 202 |
| 2×25 RM + 2×1,5 RE | 1.200/12.100 | 3.8 | 107 | 18.0 | 249 |
| 4×25 RM | 1.200 | 3.8 | 107 | 21.7 | 404 |
| 4×25 RM + 2×1,5 RE | 1.200/12.100 | 3.8 | 107 | 21.7 | 451 |
| 2×35 RM | 0.868 | 5.2 | 132 | 20.8 | 269 |
| 2×35 RM + 2×1,5 RE | 0.868/12.100 | 5.2 | 132 | 20.8 | 316 |
| 4×35 RM | 0.868 | 5.2 | 132 | 25.1 | 539 |
| 4×35 RM + 2×1,5 RE | 0.868/12.100 | 5.2 | 132 | 25.1 | 586 |
| 2×50 RM | 0.641 | 7.6 | 165 | 23.4 | 352 |
| 2×50 RM + 2×1,5 RE | 0.641/12.100 | 7.6 | 165 | 23.4 | 399 |
| 1×54.6 RM + 3×25 RM | 0.630/1.200 | 3.8 | 107 | 21.7 | 507 |
| 1×54.6 RM + 3×25 RM + 1×16 RM | 0.630/1.200/1.910 | 3.8/2.3 | 107/72 | 24.3 | 573 |
| 1×54.6 RM + 3×25 RM + 2×16 RM | 0.630/1.200/1.910 | 3.8/2.3 | 107/72 | 29.7 | 639 |
| 1×54.6 RM + 3×25 RM + 3×16 RM | 0.630/1.200/1.910 | 3.8/2.3 | 107/72 | 31.1 | 705 |
| 1×54.6 RM + 3×35 RM | 0.630/0.868 | 5.2 | 132 | 25.1 | 615 |
| 1×54.6 RM + 3×35 RM + 1×16 RM | 0.630/0.868/1.910 | 5.2/2.3 | 132/72 | 28.1 | 680 |
| 1×54.6 RM + 3×35 RM + 2×16 RM | 0.630/0.868/1.910 | 5.2/2.3 | 132/72 | 34.3 | 748 |
| 1×54.6 RM + 3×35 RM + 3×16 RM | 0.630/0.868/1.910 | 5.2/2.3 | 132/72 | 35.9 | 814 |
| 1×54.6 RM + 3×35 RM + 1×25 RM | 0.630/0.868/1.200 | 5.2/3.8 | 132/107 | 28.1 | 714 |
| 1×54.6 RM + 3×50 RM | 0.630/0.641 | 7.6 | 165 | 28.2 | 741 |
| 1×54.6 RM + 3×50 RM + 1×16 RM | 0.630/0.641/1.910 | 7.6/2.3 | 165/72 | 31.6 | 806 |
| 1×54.6 RM + 3×50 RM + 2×16 RM | 0.630/0.641/1.910 | 7.6/2.3 | 165/72 | 38.6 | 875 |
| 1×54.6 RM + 3×50 RM + 3×16 RM | 0.630/0.641/1.910 | 7.6/2.3 | 165/72 | 40.4 | 940 |
| 1×54.6 RM + 3×50 RM + 1×25 RM | 0.630/0.641/1.200 | 7.6/3.8 | 165/107 | 31.6 | 841 |
| 1×54.6 RM + 3×70 RM | 0.630/0.443 | 10.2 | 205 | 33.0 | 950 |
| 1×54.6 RM + 3×70 RM + 1×16 RM | 0.630/0.443/1.910 | 10.2/2.3 | 205/72 | 37.0 | 1014 |
| 1×54.6 RM + 3×70 RM + 2×16 RM | 0.630/0.443/1.910 | 10.2/2.3 | 205/72 | 45.2 | 1083 |
| 1×54.6 RM + 3×70 RM + 3×16 RM | 0.630/0.443/1.910 | 10.2/2.3 | 205/72 | 47.3 | 1148 |
| 1×54.6 RM + 3×70 RM + 1×25 RM | 0.630/0.443/1.200 | 10.2/3.8 | 205/107 | 37.0 | 1048 |
| 1×54.6 RM + 3×70 RM + 2×25 RM | 0.630/0.443/1.200 | 10.2/3.8 | 205/107 | 45.2 | 1150 |
| 1×54.6 RM + 3×70 RM + 3×25 RM | 0.630/0.443/1.200 | 10.2/3.8 | 205/107 | 47.3 | 1250 |
| 1×54.6 RM + 3×95 RM | 0.630/0.320 | 13.5 | 240 | 37.4 | 1176 |
| 1×54.6 RM + 3×95 RM + 1×16 RM | 0.630/0.320/1.910 | 13.5/2.3 | 240/72 | 41.9 | 1243 |
other cross-sections on request
| Number of Cores x Nominal Cross Section | Overal Diameter | Weight | Maximum Conductor Resistance | Minimum Breaking Load | Current Rating |
| No.x mm^2 | mm | Kg/Km | Ω/Km | KN | A |
| 2×10 RM | 12.8 | 93 | 3.08 | 1.5 | 38 |
| 4×10 RM | 15.4 | 183 | 3.08 | 1.5 | 38 |
| 2×16 RM | 14.8 | 129 | 1.91 | 2.3 | 72 |
| 2×16 RN + 2×1.5 RE | 14.8 | 176 | 1.910/12.100 | 2.3 | 72 |
| 4×16 RM | 17.8 | 257 | 1.91 | 2.3 | 72 |
| 4×16 RN + 2×1.5 RE | 17.8 | 304 | 1.910/12.100 | 2.3 | 72 |
| 2×25 RM | 18 | 202 | 1.2 | 3.8 | 107 |
| 2×25 RM + 2×1.5 RE | 18 | 249 | 1.200/12.100 | 3.8 | 107 |
| 4×25 RM | 21.7 | 404 | 1.2 | 3.8 | 107 |
| 4×25 RM + 2×1.5 RE | 21.7 | 451 | 1.200/12.100 | 3.8 | 107 |
| 2×35 RM | 20.8 | 269 | 0.868 | 5.2 | 132 |
| 2×35 RM + 2×1.5 RE | 20.8 | 316 | 0.868/12.100 | 5.2 | 132 |
| 4×35 RM | 25.1 | 539 | 0.868 | 5.2 | 132 |
| 4×35 RM + 2×1.5 RE | 25.1 | 586 | 0.868/12.100 | 5.2 | 132 |
| 2×50 RM | 23.4 | 352 | 0.641 | 7.6 | 165 |
| 2×50 RM + 2×1.5 RE | 23.4 | 399 | 0.641/12.100 | 7.6 | 165 |
| 1×54.6 RM + 3×25 RM | 21.7 | 507 | 0.630/1.200 | 3.8 | 107 |
| 1×54.6 RM + 3×25 RM + 1×16 RM | 24.3 | 573 | 0.630/1.200/1.910 | 3.8/2.3 | 107/72 |
| 1×54.6 RM + 3×25 RM + 2×16 RM | 29.7 | 639 | 0.630/1.200/1.910 | 3.8/2.3 | 107/72 |
| 1×54.6 RM + 3×25 RM + 3×16 RM | 31.1 | 705 | 0.630/1.200/1.910 | 3.8/2.3 | 107/72 |
| 1×54.6 RM + 3×35 RM | 25.1 | 615 | 0.630/0.868 | 5.2 | 132 |
| 1×54.6 RM + 3×35 RM + 1×16 RM | 28.1 | 680 | 0.630/0.868/1.910 | 5.2/2.3 | 132/72 |
| 1×54.6 RM + 3×35 RM + 2×16 RM | 34.3 | 748 | 0.630/0.868/1.910 | 5.2/2.3 | 132/72 |
| 1×54.6 RM + 3×35 RM + 3×16 RM | 35.9 | 814 | 0.630/0.868/1.910 | 5.2/2.3 | 132/72 |
| 1×54.6 RM + 3×35 RM + 1×25 RM | 28.1 | 714 | 0.630/0.868/1.200 | 5.2/3.8 | 132/107 |
| 1×54.6 RM + 3×50 RM | 28.2 | 741 | 0.630/0.641 | 7.6 | 165 |
| 1×54.6 RM + 3×50 RM + 1×16 RM | 31.6 | 806 | 0.630/0.641/1.910 | 7.6/2.3 | 165/72 |
| 1×54.6 RM + 3×50 RM + 2×16 RM | 38.6 | 875 | 0.630/0.641/1.910 | 7.6/2.3 | 165/72 |
| 1×54.6 RM + 3×50 RM + 3×16 RM | 40.4 | 940 | 0.630/0.641/1.910 | 7.6/2.3 | 165/72 |
| 1×54.6 RM + 3×50 RM + 1×25 RM | 31.6 | 841 | 0.630/0.641/1.200 | 7.6/3.8 | 165/107 |
| 1×54.6 RM + 3×70 RM | 33 | 950 | 0.630/0.443 | 10.2 | 205 |
| 1×54.6 RM + 3×70 RM + 1×16 RM | 37 | 1014 | 0.630/0.443/1.910 | 10.2/2.3 | 205/72 |
| 1×54.6 RM + 3×70 RM + 2×16 RM | 45.2 | 1083 | 0.630/0.443/1.910 | 10.2/2.3 | 205/72 |
| 1×54.6 RM + 3×70 RM + 3×16 RM | 47.3 | 1148 | 0.630/0.443/1.910 | 10.2/2.3 | 205/72 |
| 1×54.6 RM + 3×70 RM + 1×25 RM | 37 | 1048 | 0.630/0.443/1.200 | 10.2/3.8 | 205/107 |
| 1×54.6 RM + 3×70 RM + 2×25 RM | 45.2 | 1150 | 0.630/0.443/1.200 | 10.2/3.8 | 205/107 |
| 1×54.6 RM + 3×70 RM + 3×25 RM | 47.3 | 1250 | 0.630/0.443/1.200 | 10.2/3.8 | 205/107 |
| 1×54.6 RM + 3×95 RM | 37.4 | 1176 | 0.630/0.320 | 13.5 | 240 |
| 1×54.6 RM + 3×95 RM + 1×16 RM | 41.9 | 1243 | 0.630/0.320/1.910 | 13.5/2.3 | 240/72 |
| No. of Cores and Section | No. of Wires | Nominal Insulation Thickness | Approx. Diameter of Cable |
Max. DC. Resistance at 20℃ | Approx. Weight |
| mm² | No. | mm | mm | Ω/km | kg/km |
| 2×16 | 7 | 1.2 | 14.4 | 1.91 | 131 |
| 2×25 | 7 | 1.4 | 17.6 | 1.20 | 200 |
| 2×35 | 7 | 1.6 | 20.4 | 0.868 | 273 |
| 2×50 | 7 | 1.6 | 22.6 | 0.641 | 350 |
| 2×70 | 12 | 1.8 | 26.8 | 0.443 | 495 |
| 2×95 | 19 | 1.8 | 30.4 | 0.320 | 656 |
| 2×120 | 19 | 1.8 | 32.8 | 0.253 | 799 |
| 4×16 | 7 | 1.2 | 17.4 | 1.91 | 262 |
| 4×25 | 7 | 1.4 | 21.3 | 1.20 | 399 |
| 4×35 | 7 | 1.6 | 24.7 | 0.868 | 547 |
| 4×50 | 7 | 1.6 | 27.3 | 0.641 | 699 |
| 4×70 | 12 | 1.8 | 32.4 | 0.443 | 990 |
| 4×95 | 19 | 1.8 | 36.8 | 0.320 | 1311 |
| 4×120 | 19 | 1.8 | 39.7 | 0.253 | 1597 |
| No. of Cores and Section | No. of Wires | Nominal Insulation Thickness | Approx. Diameter of Cable |
Max. DC. Resistance at 20℃ | Approx. Weight | |||
| Phase | Neutral | Phase | Neutral | Phase | Neutral | |||
| mm² | No. | No. | mm | mm | mm | Ω/km | Ω/km | kg/km |
| 1×25+1×54.6 | 7 | 7 | 1.4 | 1.6 | 21.3 | 1.20 | 0.63 | 309 |
| 1×35+1×54.6 | 7 | 7 | 1.6 | 1.6 | 22.7 | 0.868 | 0.63 | 345 |
| 1×50+1×54.6 | 7 | 7 | 1.6 | 1.6 | 23.8 | 0.641 | 0.63 | 384 |
| 1×70+1×54.6 | 12 | 7 | 1.8 | 1.6 | 25.9 | 0.443 | 0.63 | 456 |
| 1×95+1×54.6 | 19 | 7 | 1.8 | 1.6 | 27.7 | 0.320 | 0.63 | 537 |
| 1×70+1×70 | 12 | 7 | 1.8 | 1.6 | 26.7 | 0.443 | 0.50 | 491 |
| 1×95+1×70 | 19 | 7 | 1.8 | 1.6 | 28.5 | 0.320 | 0.50 | 571 |
| 1×120+1×70 | 19 | 7 | 1.8 | 1.6 | 29.7 | 0.253 | 0.50 | 643 |
| 1×120+1×95 | 19 | 19 | 1.8 | 1.6 | 31.9 | 0.253 | 0.343 | 737 |
| 1×150+1×95 | 19 | 19 | 1.8 | 1.6 | 33.6 | 0.206 | 0.343 | 819 |
| 3×25+1×54.6 | 7 | 7 | 1.4 | 1.6 | 23.5 | 1.20 | 0.63 | 508 |
| 3×35+1×54.6 | 7 | 7 | 1.6 | 1.6 | 26.1 | 0.868 | 0.63 | 619 |
| 3×50+1×54.6 | 7 | 7 | 1.6 | 1.6 | 28.1 | 0.641 | 0.63 | 733 |
| 3×70+1×54.6 | 12 | 7 | 1.8 | 1.6 | 31.9 | 0.443 | 0.63 | 951 |
| 3×95+1×54.6 | 19 | 7 | 1.8 | 1.6 | 35.2 | 0.320 | 0.63 | 1192 |
| 3×70+1×70 | 12 | 7 | 1.8 | 1.6 | 32.4 | 0.443 | 0.50 | 986 |
| 3×95+1×70 | 19 | 7 | 1.8 | 1.6 | 35.6 | 0.320 | 0.50 | 1227 |
| 3×120+1×70 | 19 | 7 | 1.8 | 1.6 | 37.8 | 0.253 | 0.50 | 1441 |
| 3×120+1×95 | 19 | 19 | 1.8 | 1.6 | 39.1 | 0.253 | 0.343 | 1536 |
| 3×150+1×95 | 19 | 19 | 1.8 | 1.6 | 42.2 | 0.206 | 0.343 | 1779 |
| No. of Cores and Section | No. of Wires | Nominal Insulation Thickness | Approx. Diameter of Cable |
Max. DC. Resistance at 20℃ | Approx. Weight | ||||||
| Phase | Neutral | Street Light | Phase | Neutral | Street Light | Phase | Neutral | Public lighting | |||
| mm² | No. | No. | No. | mm | mm | mm | mm | Ω/km | Ω/km | Ω/km | kg/km |
| 3×25+1×54.6+1×16 | 7 | 7 | 7 | 1.4 | 1.6 | 1.2 | 30.1 | 1.20 | 0.63 | 1.91 | 571 |
| 3×35+1×54.6+1×16 | 7 | 7 | 7 | 1.6 | 1.6 | 1.2 | 32.9 | 0.868 | 0.63 | 1.91 | 682 |
| 3×50+1×54.6+1×16 | 7 | 7 | 7 | 1.6 | 1.6 | 1.2 | 35.1 | 0.641 | 0.63 | 1.91 | 797 |
| 3×70+1×54.6+1×16 | 12 | 7 | 7 | 1.8 | 1.6 | 1.2 | 39.3 | 0.443 | 0.63 | 1.91 | 1014 |
| 3×70+1×54.6+1×25 | 12 | 7 | 7 | 1.8 | 1.6 | 1.4 | 39.3 | 0.443 | 0.63 | 1.20 | 1049 |
| 3×70+1×70+1×16 | 12 | 7 | 7 | 1.8 | 1.6 | 1.2 | 40.1 | 0.443 | 0.50 | 1.91 | 1049 |
| 3×95+1×70+1×16 | 19 | 7 | 7 | 1.8 | 1.6 | 1.2 | 43.7 | 0.320 | 0.50 | 1.91 | 1290 |
| 3×120+1×70+1×16 | 19 | 7 | 7 | 1.8 | 1.6 | 1.2 | 46.1 | 0.253 | 0.50 | 1.91 | 1504 |
| 3×120+1×95+1×16 | 19 | 19 | 7 | 1.8 | 1.6 | 1.2 | 48.3 | 0.253 | 0.343 | 1.91 | 1598 |
| 3×150+1×95+1×16 | 19 | 19 | 7 | 1.8 | 1.6 | 1.2 | 51.7 | 0.206 | 0.343 | 1.91 | 1842 |
| 3×25+1×54.6+2×16 | 7 | 7 | 7 | 1.4 | 1.6 | 1.2 | 30.1 | 1.20 | 0.63 | 1.91 | 637 |
| 3×35+1×54.6+2×16 | 7 | 7 | 7 | 1.6 | 1.6 | 1.2 | 32.9 | 0.868 | 0.63 | 1.91 | 748 |
| 3×50+1×54.6+2×16 | 7 | 7 | 7 | 1.6 | 1.6 | 1.2 | 35.1 | 0.641 | 0.63 | 1.91 | 862 |
| 3×70+1×54.6+2×16 | 12 | 7 | 7 | 1.8 | 1.6 | 1.2 | 39.3 | 0.443 | 0.63 | 1.91 | 1080 |
| 3×70+1×54.6+2×25 | 12 | 7 | 7 | 1.8 | 1.6 | 1.4 | 39.3 | 0.443 | 0.63 | 1.20 | 1148 |
| 3×70+1×70+2×16 | 12 | 7 | 7 | 1.8 | 1.6 | 1.2 | 40.1 | 0.443 | 0.50 | 1.91 | 1114 |
| 3×95+1×70+2×16 | 19 | 7 | 7 | 1.8 | 1.6 | 1.2 | 43.7 | 0.320 | 0.50 | 1.91 | 1356 |
| 3×120+1×70+2×16 | 19 | 7 | 7 | 1.8 | 1.6 | 1.2 | 46.1 | 0.253 | 0.50 | 1.91 | 1570 |
| 3×120+1×95+2×16 | 19 | 19 | 7 | 1.8 | 1.6 | 1.2 | 48.3 | 0.253 | 0.343 | 1.91 | 1664 |
| 3×150+1×95+2×16 | 19 | 19 | 7 | 1.8 | 1.6 | 1.2 | 51.7 | 0.206 | 0.343 | 1.91 | 1907 |
| Designation | Conductor | Average Thickness of Insulation (prescribed value) | Core Outside Diameter |
||||||
| Nature | Nominal Section | No. of Wires | Max. DC Resistance at 20 0C | Conductor Diameter |
Breaking Force | ||||
| (mm²) | No. | (Ω/km) | Min. (mm) | Max. (mm) | Min. (daN) | (mm) | Min. (mm) | Max. (mm) | |
| Phase or neutral or public lighting | 16 | 7 | 1.91 | 4.6 | 5.1 | 190 | 1.2 | 7.0 | 7.8 |
| 25 | 7 | 1.20 | 5.8 | 6.3 | 300 | 1.4 | 8.6 | 9.4 | |
| 35 | 7 | 0.868 | 6.8 | 7.3 | — | 1.6 | 10.0 | 10.9 | |
| 50 | 7 | 0.641 | 7.9 | 8.4 | — | 1.6 | 11.1 | 12.0 | |
| 70 | 12 | 0.443 | 9.7 | 10.2 | — | 1.8 | 13.3 | 14.2 | |
| 95 | 19 | 0.320 | 11.0 | 12.0 | — | 1.8 | 14.6 | 15.7 | |
| 120 | 19 | 0.253 | 12.0 | 13.1 | — | 1.8 | 15.6 | 16.7 | |
| 150 | 19 | 0.206 | 13.9 | 15.0 | — | 1.8 | 17.3 | 18.6 | |
| Neutral | 54.6 | 7 | 0.63 | 9.2 | 9.6 | 1660 | 1.6 | 12.3 | 13.0 |
| 70 | 7 | 0.50 | 10.0 | 10.2 | 2050 | 1.6 | 12.9 | 13.6 | |
| 95 | 19 | 0.343 | 12.2 | 12.9 | 2750 | 1.6 | 15.3 | 16.3 | |
| Pilot | 1.5 | 1 | 12.1 | — | 1.5 | — | 1.2 | 3.7 | 4.2 |
PDF Download
PDF Download
Why Choose Us
Contact Us Immediately
Contact Us
- 24-hour online service
- Own factory processing
Product Category
hot-sale product
Phase conductor: Aluminum, class 2,circular compacted conductors
Phase conductor screen: Non-metallic,semi-conducting compound
Phase insulation:Cross-linked polyethylene(XLPE)
Phase insulation screen:Non-metallic,semi-conducting compound,extruded strippable grooved elastomer
Phase longitudinal water tightness: Swelling powder
Phase metallic screen: Aluminium plastic tape (AL/PET)
Phase outer sheath: Polyethylene (PE)
Messenger conductor: Stranded galvanized steel wires
Messenger insulation: Polyethylene (PE)Specification
Cable Structure: POLYETHYLENE INSULATED
Conductor: Compact stranded hard drawn Aluminium wire.
Conductor Sizes: 35 – 185 mm2
Insulation: Track resistant cross-linked polyethylene (Black)
Application: For used in primary aerial cable on pole.
ABC Cable (Aerial Bundled Cable) Supplier/Manufacturer
LV MV Aerial Bundle Cables (ABC)
Aluminum (or Aluminum Alloy)stranded conductor (compacted),
XLPE (or HDPE) insulated,
AAC messenger core (AAAC or ACSR or Galvanized steel wire messenger core, bare or covered)
Twisted (or parallel) power cable
And we can still produce the cables according to the request or customers.